No. |
Item |
Unit |
Value |
1 |
Rated voltage |
kV |
12 |
2 |
Rated current |
A |
630 |
3 |
Rated frequency |
Hz |
50 |
4 |
Short-time power frequency withstand voltage |
kV |
42 |
5 |
Lighting impluse withstand voltage |
kV |
75 |
6 |
Rated short-time withstand current |
kA |
20 |
7 |
Rated duration of short circuit |
S |
4 |
8 |
Rated withstand current(peak) |
kA |
50 |
9 |
Rated short circuit making current |
kA |
50 |
10 |
Rated active load breaking current |
A |
630 |
11 |
Rated closed-loop breaking current |
A |
630 |
12 |
Rated breaking current of cable charging |
A |
10 |
13 |
Rated breaking current of non-load transformer |
A |
100 |
14 |
★Rated breaking current of single capacitor bank |
A |
500 |
15 |
★Rated breaking current of back-to-back capacitor bank |
A |
400 |
16 |
Rated mechanical endurance |
Times |
10000 |
17 |
Closing force due to bellow and atmosphere |
N |
80±30 |
18 |
Force required to hold contacts open at full stroke |
N |
150±30 |
19 |
Circuit resistance at lowest rated contact force |
μΩ |
≤30 |
20 |
Rated limit erosion |
mm |
3 |
21 |
Gas pressure inside vacuum interrupter |
Pa |
≤1×10-3 |
22 |
Weight of moving parts |
kg |
0.56 |
23 |
Weight of vacuum interrupter |
kg |
1.64 |
24 |
Clearance between open contacts |
mm |
8.5±1 |
25 |
Average opening speed |
m/s |
1.1±0.2 |
26 |
Average closing speed |
m/s |
0.6±0.2 |
27 |
Rated pressure force of contact |
N |
700±50 |
28 |
Contact bouncing duration at closing operation |
ms |
≤2 |
29 |
Closing and opening non-simultaneity of three-phase contacts |
ms |
≤2 |
30 |
Rebound amplitude of opening contacts |
mm |
≤2 |
31 |
Note:★Rated characteristics to be given on request |